Mode 1: DIRECT function (pict. 5).
The main parameters in this kind of function are Set Point (St1) and differential (P1). In the
Direct function mode the regulator opposes the controlled parameter only if it exceeds the
Set Point value. Having once fixed the desired Set Point (St1), the outputs will be energized
one by one as the parameter deviates from St1. As shown in the picture, the relays in the
models with more outputs are equally distributed within each single set differential.When
the controlled parameter is equal to/higher than St1+P1, all outputs energize.Viceversa, if
the parameter, starting from values higher than St1, starts to decrease, any active relay will
be deactivated as approaching St1.When the St1 value is reached, all outputs will be
disenergized.The DIRECT led will flash periodically, once for each activated output.
Mode 2: REVERSE function mode (pict. 6).
This is the previously described factory-set mode.
Mode 3: Dead-Band function mode (pict. 7).
The main parameters in this kind of function mode are Set Point (St1), Reverse mode
differential (P1), Direct mode differential (P2) and Dead-Band (P3). The aim of the regulator
is to bring the controlled parameter within a limited range, called dead zone, set around the
Set Point (St1). As shown in the picture, the dead zone value depends on the P3 parameter
value.Within the dead zone the instrument does not require the intervention of any device.
Outside the dead zone the instrument will work in DIRECT mode, when the controlled
parameter increases and, in REVERSE mode, when it decreases. According to the used
model, there can be one or more relays in Direct and Reverse function. Said outputs are
activated/deactivated according to the procedures already shown in modes 1 and 2,
according to the values of the controlled parameter, of St1 value, of P1 and of P2.The
DIRECT led and REVERSE led indicators will flash as already described. W
arning: when
the instrument has only one relay output, it will work in REVERSE mode with Dead-Band.
45
Advanced set-up: Function Modes description
+05-3015 • rel.3.0 interno ok 18-09-2002 14:31 Pagina 45

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel universal infrared series and is the answer not in the manual?

Carel universal infrared series Specifications

General IconGeneral
BrandCarel
Modeluniversal infrared series
CategoryController
LanguageEnglish

Related product manuals