In Function Modes 1, 2, 3, 4 and 5 there is only one Set Point, the procedure to modify it
has already been described on page 40.
In Function Modes 6, 7, 8 and 9 the instrument works with 2 Set Points.To modify both Set
Points follow these instructions (see pictures 1 and 2):
a) press the “5” key for some seconds: the display will show St1;
b) release “5”: the present value of St1 begins to flash;
c) press either “7” or “8” keys until you reach the desired value;
d) press “5” to confirm the newly set value of St1;
e) after having confirmed St1, the display shows the St2 code for some seconds, and then
the present value of Set point 2 begins to flash;
f) press either “7” or “8” until you reach the desired value;
g) press “5” to confirm St2;
h) the display shows again the value read by the main probe.
51
Advanced set-up: Function Mode modification with 2 Set Point
+05-3015 • rel.3.0 interno ok 18-09-2002 14:31 Pagina 51