Messages Description Cause Solution
Er0 probe error probe cable interrupted check connections
or short-circuited between instrum.&probe
connection error check probe signal
faulty probe (eg. NTC=10KΩ @25°C)
Er1 probe error see above but for see above but for
(NTC only) NTC2 probe NTC2 NTC2 probe
Er2 memory error supply cut off turn off then turn on
during programming he instrument again
step holding down key “6”
electrical noise if persists, replace the unit
Er3 external alarm digital input contact special function: see
open parameter C29
check external contact
Er4 HIGH alarm input has exceeded P26 check parameters
for more than P28 P26 and P28
Er5 LOW alarm input is below P25 for check parameters
more than P28 P25 & P28
Warning: In case of alarm condition, the buzzer and the alarm code must be manually
reset pressing the key ‘6’ (note:the alarm code will disappear only if the alarm is not still
pending).The alarm relay (Mode 5 only) is automatically reset when the alarm disappears;
it can need a manual reset only for special value of P27 (Er4 & Er5) and of C29 (Er3) (see
the technical manual for details). In case of alarm type Er0, Er1, Er2 the normal function
of the unit restarts automatically when the alarm disappears; after a Er3 alarm the unit
restarts automatically or manually according to C29; Er4 & Er5 alarms do not affect the
normal function of the unit.