59
Inputs
according to model (see pag 32): T
emperature: NTC, Pt100, K/J Thermoc.
Current 4/20 mA or 0/20 mA
Voltage -0,4/+1 Vdc
Operating range: NTC: -50/90 °C, Pt100: -100/600 °C,
ThcK
: -100/999 °C, ThcJ: -100/800 °C
Current/Voltage: see parameters C15 and C16
Resolution: 0.1or 1, according to decimal point selection
Controler accuracy: ± 0.5 % of maximum range
Power supply
Voltage IR32D
, W and Z: from 12 to 24 Vac-dc ±10%
IR32V: see pag.1 field ‘d’, tolerance±10%
IRDRV and W: 24 Vac± 10% and 230 Vac ± 15%
IRDR
TE: 230 Vac ± 15%
IRDRA and Z: from 12 to 24 Vac-dc, ± 10%
Power consumption: IR32A, D and V:2VA; IR32W and IR32Z: 3VA
IRDRTE, IRDRV, IRDRW and IRDRA:3VA
IRDRZ
:4VA
Probe power supply output: 10 Vdc, @ max 30mA (8Vdc for IRDRW)
Conditions of use
Working temperature: 0 ÷ 50 °C
Storage temperature: -10 ÷ 70 °C
Relative ambient humidity: lower than 90%rH, not condensing
Ambient pollution: normal
Technical specifications
+05-3015 • rel.3.0 interno ok 18-09-2002 14:31 Pagina 59

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carel universal infrared series and is the answer not in the manual?

Carel universal infrared series Specifications

General IconGeneral
BrandCarel
Modeluniversal infrared series
CategoryController
LanguageEnglish

Related product manuals