As previously explained, the Infrared series instruments are supplied ready to use, with
pre-selected Mode 2 (Reverse function).
If this kind of function is not compatible with the required use, it can be easily modified by
following these instructions (see pict.1 and 2):
a) press the “5” and “6” keys simultaneously for 5 seconds;
b) the display shows 0;
c) select the password by pressing the “7” key up to 22;
d) press the “5” key to confirm the password;
e) if the selected password is correct, the display will show the code “C0”, otherwise you
will have to repeat the instructions from point a).
C0 is the parameter corresponding to the “Function Mode”.To load one of the 9 described
Modes it is sufficient to give C0 the chosen Mode number, according to the following
instructions:
f) when C0 is displayed, press the “5” key;
g) the display shows the present Function Mode;
h) press either “7” or “8” keys until you reach the desired Function Mode; press “5” to
confirm;
i) press the “6” key to end procedure and memorise the new function mode.
50
Advanced set-up: Function mode modification
+05-3015 • rel.3.0 interno ok 18-09-2002 14:31 Pagina 50