APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
OPT1
UNIT OPTIONS 1 HARDWARE
MLV.S YES/NO Minimum Load Valve Select
Default:
YES = Factory Equipped
NO = Not Equipped
CSB.E ENBL/DSBL CSB Boards Enable
Default: ENBL
SPT.S ENBL/DSBL Space Temp Sensor Default: DSBL
SP.O.S ENBL/DSBL Space Temp Offset Enable
Default: DSBL
SP.O.R XX ǻF (ǻC) Space Temp Offset Range
Range: 1 to 10 ǻF (0.6 to 5.6 ǻC)
Default: 5 ǻF (2.8 ǻC)
RAT.T X RAT Thermistor Type
Range 0 to 2
0 = 5 k:
1 = 10 k:
2 = None
Default: 0
SAT.T X SAT Thermistor Type
Range 0 to 2
0 = 5 k:
1 = 10 k:
2 = None
Default: 0
EMM YES/NO EMM Module installed
Default:
YES = Factory Equipped
NO = Not Equipped
OPT2
UNIT OPTIONS 2 CONTROLS
C.TYP X Machine Control Type
Range: 1 to 9
1 = VAV
2 = Invalid
3 = Tstat Multi
4 = Tstat 2 Stg
5 = SPT Multi
6 = Invalid
7 = Pct Cap
8 = Dual Tstat
9 = VAV Setpoint
Default: 4
CTRL X Control Method
Range: 0 to 3
0 = Switch
1 = Occupancy
2 = Occupancy
3 = CCN Control
Default: 0
LOAD X Loading Sequence Select
Range: 1 to 2
1 = Equal
2 = Staged
Default: 1
LLCS X Lead/Lag Circuit Select
Range: 1 to 3
1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
Default: 1
DELY XX MIN Minutes Off Time
Range: 0 to 15 Minutes
Default: 0