184
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
M.MST
MOTORMASTER
MMR.S YES/NO Motormaster Select
Default:
YES = Factory Equipped
NO = Not Equipped
P.GAN XX Head Pressure P Gain
Range: –20 to 20
Default: 1.0
I.GAN XX.X Head Pressure I Gain
Range: –20 to 20
Default: 1.0
D.GAN XX.X Head Pressure D Gain
Range: –20 to 20
Default: 1.0
MIN.S XXX.X% Minimum Fan Speed
Range 0 to 100%
Default: 8%
RSET
RESET COOL TEMP
CRST X Cooling Reset Type
Range: 0 to 4
0 = No Reset
1 = 4-20 Input
2 = Out Air Temp
3 = Return (Not Supported)
4 = Space Temp
Default: 0
MA.DG XX.X ǻF (ǻC) 4-20 – Degrees Reset
Range: –30 to 30 ǻF (–16.7 to 16.7 ǻC)
Default: 10.0 ǻF (5.6 ǻC)
RM.NO XXX.X °F (°C) Remote – No Reset Temp
Range: 0.0 to 125.0 F (17.8 to 51.7 C)
Default: 10.0 F (–12.2 C)
RM.F XXX.X °F (°C) Remote – Full Reset Temp
Range: 0.0 to 125.0 F (17.8 to 51.7 C)
Default: 10.0 F (–12.2 C)
RM.DG XX.X ǻF (ǻC) Remote – Degrees Reset
Range: –30 to 30 ǻF (–16.7 to 16.7 ǻC)
Default: 0.0 ǻF (0.0 ǻC)
RT.NO XX.X ǻF (ǻC) Return – No Reset Temp
Feature Not Supported
Range: 0.0 to 30.0 ǻF (0.0 to 16.7 ǻC)
Default: 10.0 ǻF (5.6 ǻC)
RT.F XX.X ǻF (ǻC) Return – Full Reset Temp
Feature Not Supported
Range: 0.0 to 10.0 ǻF (0.0 to 5.6 ǻC)
Default: 0.0 ǻF (0.0 ǻC)
RT.DG XX.X ǻF (ǻC) Return – Degrees Reset
Feature Not Supported
Range: –30.0 to 30.0 ǻF (–16.7 to 16.7 ǻC)
Default: 0.0 ǻF (0.0 ǻC)
DMDC X Demand Limit Select
Range: 0 to 3
0 = None
1 = Switch
2 = 4-20 Input
3 = CCN Loadshed
Default: 0
DM20 XXX% Demand Limit at 20 mA
Range: 0 to 100%
Default: 100%
SHNM XX Loadshed Group Number
Range: 0 to 99
Default: 0
SHDL XX% Loadshed Demand Delta
Range: 0 to 60%
Default: 0%
SHTM XXX min Maximum Loadshed Time
Range: 0 to 120 Minutes
Default: 60 Minutes
DLS1 XXX% Demand Limit Switch 1
Range: 0 to 100%
Default: 80%
DLS2 XXX% Demand Limit Switch 2
Range: 0 to 100%
Default: 50%
SLCT
SETPOINT AND RAMP LOAD
RL.S ENBL/DSBL Ramp Load Select
Default: Enable
CRMP ENBL/DSBL Cooling Ramp Loading
Default: 1.0
Range: 0.3 to 2
SCHD XX Schedule Number
Default: 1
Range: 1 to 99
Z.GN X.X Deadband Multiplier
Default: 1
Range: 1 to 4