Carrier Standing Type Inverter Air Conditioner
● Using a leakage tester or soapy water check for leakages at the joint.
Leakage detector
Air purge
Procedure of air purge
Gas leakage check
three way valve (gas)
needle valve
valve cap
valve needle
allen (hex. head) wrench
two way valve (liquid)
flare nut
liquid pipe (small diameter)
⑨ gas pipe (large diameter)
⑩ indoor unit
⑪ outdoor unit
⑫ vacuum pump
● For air purge, use a vacuum pump.
● Do not use the compressor in the outdoor unit as a vacuum pump.
● Do not use the refrigerant in the unit to remove the air inside the pipes.
● No additional refrigerant for air purge.
① Connect the gauge manifold and the vacuum pump.
Operate the vacuum pump connected to three way valve until the pressure
reaches 50Pa (0.5mbar).
Open the valve on the liquid side for about three seconds and close it again
quickly. Check for leakages.
④ After checking for leakages, fully open the three way valve.
⑤ Close the cap and check for leakages.
When all the pipe connection tasks are finished, use a HFC refrigerant leakage
detector to check for leakages.
When all the connections are made, use soapy water to check leakage. Wrap the
joint with insulations and tapes.
Caution
38
CONNECTING THE PIPES