User / Install Manual
PRODUCT SPEC / CONNECTION PIPE / REFRIGERANT CHARGING
Type Cooling Only Heat Pump
Electric (V-ph-Hz) 220-1-50
Cooling capacity (Btu/h) 21000
18000
Heating capacity (Btu/h)
- 18100
Product size
(mm)
Indoor unit (WxHxD) 340 x 1884 x 340
Outdoor unit (WxHxD) 780 x 550 x 290
Product specification
Connection pipe
Pipe diameter(mm) Pipe diameter(inch)
Gas pipe Liquid pipe Gas pipe Liquid pipe
12.7 6.35 1/2 1/4
Refrigerant charging
Caution : This product uses R410A refrigerant. (Do not mix with R22 refrigerant)
If the amount of refrigerant is reduced due to leakages or repairs, recover all
refrigerant from the unit and charge the designated amount by using a vacuum
pump.
This is the inverter air conditioner whose compressor speed varies depending
on its working conditions. So, do not add or reduce refrigerant based on the
discharge/suction pressure.
● When the length of connection pipe is over 5m, add 20g of refrigerant per extra meter
from 5m.
For example: for 11m connection pipe, (11-5) x 20 = 120g to add