SRDC-UG-2-14-000
REVISION
DATE
PAGE
19 Series Carrier®
SmartVu
TM
Controls IOM
2.3
Dec 4, 2020
143 OF 168
143
25
ctrlw_dt
-
0.00
0
^C
^F
Controlled Water DT
26
cdw_fl_s
0 to 2
0
-
Cond Flow Status
27
blank
-
-
-
Failed or Not Started=0
28
blank
-
-
-
Success=1, Verifying=2
29
chw_fl_s
0 to 2
0
-
Chilled Flow Status
30
blank
-
-
-
Failed or Not Started=0
31
blank
-
-
-
Success=1, Verifying=2
32
pdown_st
0 to 255
0
-
Pumpdown/Lockout State
*Depends on the selected language (English by default).
RUNTIME - Run Times
Name
Range
Default
Unit
Displayed text*
1
ST_CNT12
-
0
-
Starts Num in 12 Hours
2
C_STARTS
0 to 65535
0
-
Compressor Starts Num
3
COMP_MIN
0 to 99999999
0
min
Comp Running Time
4
COMP_HRS
0 to 500000
0
hours
Comp Total Running Hrs
5
SRV_HRS
0 to 500000
0
hours
After Service Hrs
6
spst_tim
-
0
min
Stop to Start Timer
7
stst_tim
-
0
min
Start to Start Timer
8
oilb_dur
-
0
hours
Oil Lubrication Duration
9
oilstdur
-
0
hours
Oil Storage Duration
10
RCYSTCNT
-
0
-
Recy Startup in 4 Hours
11
SWIFTCNT
-
0
-
Swift Restarts in 1 Hour
12
PGP_NO
-
0
-
Total Pumpout Numbers

Table of Contents