SRDC-UG-2-14-000
REVISION
DATE
PAGE
19 Series Carrier®
SmartVu
TM
Controls IOM
2.3
Dec 4, 2020
149 OF 168
149
12
tmramprt
0.56 to 5.56
1 to 10
1.67
3
^C
^F
Temp Ramp per Min
13
rcysh_dt
0.28 to 2.22
0.5 to 4
0.56
1
^C
^F
Recycle Shutdown Delta T
14
rcyst_dt
1.11 to 5.56
2 to 10
5.56
10
^C
^F
Recycle Restart Delta T
15
dmp_min
0 to 30
2
%
ECO DMP VLV Min Pos
16
dmp_max
60 to 100
85
%
ECO DMP VLV Max Pos
17
dmp_step
1.5 to 20
5
%
ECO DMP VLV Speed Step
18
dmp_intv
5 to 30
10
sec
ECO DMP VLV Out Interval
19
dmp_alm
60 to 600
180
sec
ECO DMP VLV Fault Time
20
dmp_dly
1 to 5
2
min
ECO DMP VLV Act Delay
21
dmp_cldb
13.79 to 68.95
2 to 10
34.48
5
kPa
PSI
ECO DMP VLV Close DB
22
dmp_opdb
68.95 to 137.90
10 to 20
89.64
13
kPa
PSI
ECO DMP VLV Open DB
23
dmp_gain
0 to 10
1
-
ECO DMP VLV Gain
24
dmp_dt
2.22 to 5.56
4 to 10
3.89
7
^C
^F
ECO DMP VLV Act Delta T
25
oilpvr_t
15 to 300
180
sec
Lub Press Verify Time
26
wflow_t
0.5 to 5
5
min
Water Flow Verify Time
27
sf_st_th
40 to 100
100
%
Soft Stop Amps Threshold
28
mbb_pfcl
0.5 to 2
1
-
Power Calibration Factor
29
ex_start
NO_YES
NO
-
Enable Excessive Starts
30
oilstiro
0 to 3
1
-
Oil Stir Cycle(19XR6/7)
31
blank
-
-
-
No Stir=0, 30s/30m=1,