SRDC-UG-2-14-000
REVISION
DATE
PAGE
19 Series Carrier®
SmartVu
TM
Controls IOM
2.3
Dec 4, 2020
152 OF 168
152
41
gvliftm1
-
19.50
35.1
^C
^F
DTS@GV Opening 1
42
gvstall2
-
15.5
%
GV Opening 2
43
gvliftm2
-
30.50
54.9
^C
^F
DTS@GV Opening 2
44
gv_db
-
2.5
%
GV Jumpover Range
45
gv_delay
-
5
%
GV Jumpover Delay
46
gv_sk_th
-
0.50
0.9
^C
^F
Max Temp Deviation -
47
gv_sk_tl
-
0.61
1.1
^C
^F
Max Temp Deviation +
*Depends on the selected language (English by default).
CFGLIMIT - Protective Limit
Name
Range
Default
Unit
Displayed text*
1
evap_al
0.28 to 8.33
0.5 to 15
2.78
5
^C
^F
Evap Approach Alert
2
cond_al
0.28 to 8.33
0.5 to 15
3.33
6
^C
^F
Cond Approach Alert
3
cpov_lo
620.55 to 1,082.52
90 to 157
965.30
140
kPa
PSIG
Cond Press Override Low
4
cpov_hi
1,379.00 to
1,827.18
200 to 265
1,723.75
250
kPa
PSIG
Cond Press Override High
5
cpcut_lo
1,103.20 to
1,137.68
160 to 165
1,103.20
160
kPa
PSIG
Cond Press Cutout Low