EasyManua.ls Logo

Carrier SmartVu control - Page 153

Carrier SmartVu control
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SRDC-UG-2-14-000
REVISION
DATE
PAGE
19 Series Carrier®
SmartVu
TM
Controls IOM
2.3
Dec 4, 2020
153 OF 168
153
6
cpcut_hi
1,861.65 to
1,896.13
270 to 275
1,896.13
275
kPa
PSIG
Cond Press Cutout High
7
ert_ovdt
1.11 to 2.78
2 to 5
1.67
3
^C
^F
Evap Override Delta T
8
ert_trip
-17.78 to 4.44
0 to 40
0.56
33
°C
°F
Evap Refrig Trippoint
9
high_lfp
DSABLE_ENABLE
DSABLE
-
High Lift Freeze Protect
10
ep_ov
620.55 to 1,082.52
90 to 157
965.30
140
kPa
PSIG
High Evap Press Override
11
ep_cut
1,103.20 to
1,172.15
160 to 170
1,137.68
165
kPa
PSIG
High Evap Press Cutout
12
ep_ovdv
137.90 to 386.12
20 to 56
379.23
55
kPa
PSIG
Hi Evap Pre Override DV
13
ep_cutdv
406.81 to 415.77
59 to 60.3
406.81
59
kPa
PSIG
Hi Evap Pre Cutout DV
14
cpov_dl
124.11 to 399.22
18 to 57.9
186.17
27
kPa
PSIG
Cond Pre Override DV 44
15
cpcut_dl
206.85 to 415.77
30 to 60.3
206.85
30
kPa
PSIG
Cond Pre Cutout DV 44
16
cpov_dh
137.90 to 386.12
20 to 56
379.23
55
kPa
PSIG
Cond Pre Override DV 72
17
cpcut_dh
406.81 to 415.77
59 to 60.3
406.81
59
kPa
PSIG
Cond Pre Cutout DV 72
18
cdfreeze
-28.89 to 1.67
-20 to 35
1.11
34
°C
°F
Condenser Freeze Point

Table of Contents

Related product manuals