24
7.3 -  Cooling / Heating
The Touch Pilot control can manage the whole range of 
operations ensuring the correct functioning of the air-
conditioning unit. 61XWHZE heat pumps can operate either 
in Cooling or Heating.
The unit operation is based on the following parameters:
•  Unit On/Off status: This parameter indicates whether 
the unit is shut down (not authorised to start) or in 
operation (authorised to start).
•  Control type: Indicates whether the unit operates in 
Local, Remote or Network mode.
•  Heating/Cooling selection in Local mode: The operating 
•  Heat/Cool switch status in Remote mode: These contacts 
•  Heat/Cool selection in Network mode: The network 
command [HC_SEL] permits heating/cooling control if 
the unit is in Network operating mode.
Status Control 
type
Heat/Cool 
in Local
Heat/Cool 
in Remote
Heat/Cool 
in Network
Current 
mode
o - - - - -
on local cool - - cooling
on local heat - - heating
on local - on_cool - cooling
on local - on_heat - heating
on remote - on_cool - cooling
on remote - on_heat - heating
on network - - cool cooling
on network - - heat heating
7.4 -  Control interlock contact
This contact checks the status of a loop (customer safety 
delay at start-up has expired. This open contact leads to an 
alarm shut-down, if the unit is running (alarm 10028).
7.5 -  Control point
The control point represents the water temperature that the 
unit must produce. It enables to decrease the required 
capacity depending on the unit load operating conditions. 
The heat exchanger entering water temperature is controlled 
Control point = Active setpoint + Reset
     
instead of any other setpoint calculation only when the unit 
is in the Network operating type.
7.5.1 -  Active setpoint
Two setpoints can be selected when the unit is in Heating 
mode, and three setpoints can be selected when the unit is 
in Cooling mode. The first cooling/heating setpoint is 
normally used during occupied periods and the second 
cooling/heating setpoint is used during unoccupied periods, 
whereas the third cooling setpoint is used for ice storage (ice 
Setpoint 1 Setpoint 2 Setpoint 3
Cooling  Occupied Unoccupied Ice storage cooling setpoint
Heating Occupied Unoccupied -
Depending on the current operation type (local/remote/
Main menu (Heat/Cool Select, GENUNIT) in Local mode, 
section  3.8), with network commands in Network mode 
(SP_SEL; CCN or BACnet) or automatically with the 
setpoint time schedule (schedule 2).
The following table summarises the possible setpoint selections 
based on the control type (local, remote, network) and the 
following parameters:
•  Local parameters: 
-  Heating/Cooling operating mode  
  (hc_sel, GENUNIT). 
-  Setpoint selection (sp_sel, GENUNIT).
•  Remote setpoint contacts: 
 
  (GEN_CONF, Ice_cnfg must be set to “yes”). 
-  Ice done contact from EMM (SIOB EMM board,   
  DI4_ICE_SW, by default set to “closed”). 
-  Dual setpoint switch status (spt_sw).
•  Network settings: 
-  Schedule 2 status for setpoint selection      
  (GENUNIT, SP_OCC set to “yes” or “no”).
Local operating type
Parameter status
Active 
setpoint
Mode sp_sel Ice_cnfg Ice_done spt_sw  sp_occ
cool sp-1 - * * - cooling stp 1
cool sp-2 no * * - cooling stp 2
cool sp-2 yes closed *  - cooling stp 2
cool sp-2 yes open *  - ice stp
cool auto - * * occupied cooling stp 1
cool auto no * * unoccupied cooling stp 2
cool auto yes closed * unoccupied cooling stp 2
cool auto yes open * unoccupied ice stp
heat sp-1 - * * - heating stp 1
heat sp-2 - * * - heating stp 2
heat auto - * * occupied heating stp 1
heat auto - * * unoccupied heating stp 2
Remote operating type
Parameter status
Active 
setpoint
Mode sp_sel Ice_cnfg Ice_done spt_sw  sp_occ
cool - - * open - cooling stp 1
cool - no * close - cooling stp 2
cool  - yes closed close  - cooling stp 2
cool - yes open close - ice stp
heat - - * open - heating stp 1
heat - - * close - heating stp 2
Network operating type
Parameter status
Active 
setpoint
Mode sp_sel Ice_cnfg Ice_done spt_sw  sp_occ
cool - - * * occupied cooling stp 1
cool - - * * unoccupied cooling stp 2
heat - - * * occupied heating stp 1
heat - - * * unoccupied heating stp 2
(*): any conguration    (-): default conguration
NOTE: Ice storage conguration [Ice_cnfg] and ice done 
contact [Ice_done] apply only to units with the optional 
energy management module.