28
7.15 -  Master/Slave assembly
The master unit can be controlled locally, remotely or by 
stop, setpoint selection, heating/cooling operation, load 
as the master. The commands are transmitted automatically 
units, each unit will return to an autonomous operating mode 
until the fault is cleared. If the master unit is stopped due to 
NOTE: Master/slave assembly can be congured only by 
Carrier service technicians.
7.16 -  Energy Management Module (EMM)
    
such as current unit status, compressors operating status, etc. 
This option requires the installation of an additional SIOB 
board.
Description Connector * Remarks
Occupancy 
override control
DI-01, 77-78 If the contact is closed in Remote 
mode, the unit goes into the occupied 
mode
Demand limit 
switch 2
DI-02, 
73A-74A
If the contact is closed, the second 
capacity limit switch is active
Customer 
interlock
DI-03, 
34A35A
Permits immediate unit shutdown 
(Remote mode only)
Ice storage DI-04, 75-76 If the contact is closed, the unit starts 
the ice storage mode
Space 
temperature
AI-01, 
71A-72A
Active setpoint reset via space 
temperature control
Capacity limit 
control
AI-10, 67-68 Active setpoint reset via unit capacity 
control (4-20 mA)
Compressor A DO-01, 
37A1-38A1
Output active if compressor A is 
operating
Compressor B DO-02, 
37B1-38B1
Output active if compressor B is 
operating
Chiller ready DO-04, 
30A-31A
Relay output active when the unit is 
ready to operate
Chiller in alert DO-05, 
30B-31B
Relay output active when the alert is 
tripped
Chiller 
shutdown
DO-06, 30-31 Relay output active when the unit is 
stopped due to an alarm
Unit capacity A0-01, 
79+-79-
Capacity running output (0 to10 VDC)
* Connector type:
DI = Digital Input
AI = Analogue Input
DO = Digital Output
AU = Analogue Output
7.17 -  Schedule setting
one (OCCPC01S) is used for controlling the unit start/stop, 
whereas the second one (OCCPC02S) is used for controlling 
the dual setpoint.
The rst timer  program 
automatically switch the unit from an occupied mode to an 
unoccupied mode: the unit is started during occupied periods.
The second timer program
automatically  switch the active setpoint from an occupied 
setpoint to an unoccupied setpoint: cooling or heating setpoint 1 
is used during occupied periods, cooling or heating setpoint 2 
during unoccupied periods.
The control offers the user the possibility of setting eight 
occupancy periods where each occupancy period includes the 
•  Day of the week: Select the days when the period is 
occupied.
•  Occupancy time (“occupied from” to “occupied to”): 
Set occupancy hours for the selected days.
•  Timed Override Extension: Extend the schedule if 
necessary. This parameter can be used in the case of 
Example: If the unit is normally 
scheduled to run between 8:00 to 18:00, but one day you 
want the air-conditioning system to operate longer, then set 
this timed override extension. If you set the parameter to 
“2”, then the occupancy will end at 20:00.
To set the unit start/stop schedule
1. Go to the Main menu.
2. 
and select Schedule Menu (SCHEDULE).
3. Go to OCCPC01S. 
4. Select appropriate check boxes to set the unit occupancy on 
5. 
6. When the time schedule is set, the selected period will be 
presented in the form of the green band on the timeline. 
7. Press the SaveCancel 
1 Selection of days for the time schedule
2 Start/end of the schedule
3 Save
4 Cancel
5 Previous time period
6 Next time period
1
2
3
4
5 6