No. Code Alarm description Reset type Action taken Possible cause
80 10078 Circuit A High Discharge Gas Temperature  Manual Circuit A shuts down Defective transducer, 
max. condensing 
temperature setpoint too 
low or refrigerant charge 
too high
81 10079 Circuit B High Discharge Gas Temperature  Manual Circuit B shuts down As above
82 10080 Circuit C High Discharge Gas Temperature  Not applicable to this unit
83 10081 Circuit A Suction valve closed Manual Circuit A shuts down Economizer pressure 
transducer defective, 
suction valve fault
84 10082 Circuit B Suction valve closed Manual Circuit B shuts down As above
85 10083 Circuit C Suction valve closed Not applicable to this unit
86 10087 Circuit A Slide Valve Control Unveriable  Manual None Defective or incorrectly 
wired solenoid valves, 
defective current 
transformer
87 10088 Circuit B Slide Valve Control Unveriable  Manual None As above
88 10089 Circuit C Slide Valve Control Unveriable  Not applicable to this unit
89 10090 Cooler Flow Switch Setpoint Conguration 
Failure 
Manual Unit is not allowed to restart Defective ow controller 
or wiring error
90 10091 Cooler Flow Switch Failure  Automatic (the rst alarm 
within the last 24 hours) or 
Manual
Compressors and the 
evaporator pump are stopped
As above
91 10100 Electrical Box Fan Failure Manual Unit shuts down Electrical box fan 
malfunction or fan current 
probe malfunction
92 10097 Water Exchanger Temperature Sensors 
Swapped 
Manual Unit shuts down Leaving water tempera-
ture is higher than entering 
water temperature
Maintenance alarms
93 13nnn Service Maintenance Alert Number 
001: Circuit A Loss of charge 
002: Circuit B Loss of charge
004: Water loop size warning
005: Air exchanger cleanness warning
006: Cooler pump 1 servicing required
007: Cooler pump 2 servicing required
008: Condenser pump 1 servicing required
010: Water lter servicing required
011: Compressor A oil lter servicing required
012: Compressor B oil lter servicing required
015: Replacement of expansion valve 
required on circuit A
016: Replacement of expansion valve 
required on circuit B
Manual None Preventive maintenance 
date has passed; 
servicing action required; 
contact Carrier Service 
Agency
Software failure
94 55001 Database Module Failure Manual Unit shuts down Software problem. 
Contact Carrier Service
95 56001 Lenscan Module Failure Manual Unit shuts down As above
Device failure
96 57020 Main EXV stepper motor Failure - cir A Manual Circuit A shuts down EXV motor fault
97 57021 Main EXV stepper motor Failure - cir B Manual Circuit B shuts down EXV motor fault
98 57022 Main EXV stepper motor Failure - cir C Not applicable to this unit
99 57023 EXV eco stepper motor Failure - cir A Manual Circuit A shuts down Eco EXV motor fault
100 57024 EXV eco stepper motor Failure - cir B Manual Circuit B shuts down Eco EXV motor fault
101 57025 EXV eco stepper motor Failure - cir C Not applicable to this unit
102 10050 Refrigerant Leakage Detection Automatic None Refrigerant leak or leak 
detector defective
Compressor alarms
103 1101 Compressor A Motor temperature too high  Manual Unit shuts down Motor/wiring fault
104 1102 Compressor A Motor temperature out of 
range
Manual Unit shuts down Probe defective or 
incorrect wiring