Ease of use
Large, backlit, easy to read, 5-line LCD display with wide viewing angle
Password-protected setup via front panel or free PMC Setup software
Easy installation with mounting clips, no tools required
Built in alarm buzzer for optional I residual and Temperature alarms
Setpoints
6 user programmable setpoints
Configurable thresholds, time delays and DO triggers
SOE Log
32 events time-stamped to ±1ms resolution
Setup changes, Setpoint and DI status changes and DO operations
Communications
Optically isolated RS485 port
Selectable baud rate from 1200 bps to 19,200 bps
Modbus RTU protocol
System Integration
Supported by our PecStar® Integrated Energy Management System
Easy integration into other Automation or SCADA systems
Optional features
I residual Input (Residual Current)
Requires an optional, external Zero Sequence CT (1A nominal)
Two levels of alarm – ALARM and TRIP. Each alarm level:
Can be enabled individually
Programmable threshold and time delay
Logs an SOE event, sounds the alarm buzzer AND triggers a dedicated DO when activated
RTD Temperature Input
Requires an optional, external RTD temperature probe
Programmable threshold and time delay
Logs an SOE event, sounds the alarm buzzer AND triggers a dedicated DO when activated
Digital Inputs and Outputs
Digital Inputs – 2 volts free dry contact, 24VDC internally wetted
Digital Outputs – 2 Form A DO (mechanical) or Solid State (SS) relays
2 DO relays
DO1 is for I residual or Temperature ALARM output if present AND enabled
DO2 is for I residual TRIP output if present AND enabled
2 SS relays for kWh and kvarh pulsing