3.4.4 Configuration
The Setup Configuration mode provides access to the following setup parameters:
Label
Parameters
Description
Option(value)
Default
PMC-53 Model
Menu
1
st
2
nd
V
I
M
PROGRAMMING
Setup
Configuration
Mode
/
/
PASSWORD
Password
Enter Password
/
“0”
SET PASS
Change
Password?
YES/NO
NO
NEW PASS
New Password
Change
Password
0000 to 9999
“0”
TYPE
Wiring Mode
1
The wiring
connection of
the meter
WYE/DELTA/DEMO
WYE
PT
PT Ratio
2
PT Ratio
1 to 2,200
1
CT
CT Ratio
2
CT Ratio
1 to 30,000 (1A)
1 to 6,000 (5A)
1
PF SET
P.F. Convention
3
P.F. Convention
IEC/IEEE/-IEEE
IEC
KVA SET
kVA Calculation
4
kVA Calculation
Method
V/S
V
ID
Meter Address
Meter Address
1-247
100
BAUD
Baud rate
Data rate in bits
per second
1200/2400/4800/
9600/19200bps
9600
CONFIG
Comm. Port
Configuration
Data Format
8N2/8O1/8E1/8N1/8O2
/8E2
8E1
ALARM
Configure Alarm
YES/NO
NO
IR ALM
I residual
ALARM
5
Enable I residual
ALARM
ON/OFF
ON
ALM SP
I residual
ALARM SP
5
Set I residual
ALARM Setpoint
30 -1000mA
500
ALM DLY
I residual
ALARM Delay
5
Set I residual
ALARM Delay
0 - 600(x0.1s)
20
ALM DO1
I residual
ALARM Trigger
5
Enable I residual
ALARM Trigger
(DO1)
ON/OFF
ON
IR TRP
I residual TRIP
5
Enable I residual
TRIP
ON/OFF
ON
TRP SP
I residual TRIP
SP
5
Set I residual
TRIP Setpoint
30 -1000(mA)
500
TRP DLY
I residual TRIP
Delay
5
Set I residual
TRIP Delay
0 - 600(x0.1s)
20