EasyManua.ls Logo

CET PMC-53 Series - Page 26

CET PMC-53 Series
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Ceiec Electric Technology
26
ALM TMP
Temperature
ALARM
5
Enable
Temperature
ALARM
ON/OFF
ON
TMP SP
Temperature
ALARM SP
5
Set
Temperature
ALARM Setpoint
55 -140(°C )
80
TMP DLY
Temperature
ALARM Delay
5
Set
Temperature
ALARM Delay
0 - 400(x0.1s)
20
TMP DO1
Temperature
ALARM Trigger
5
Set
Temperature
ALARM Trigger
(DO1)
ON/OFF
OFF
DI1 PRO
DI1 SP Output
Trigger
Enable DI1 SP
Output Trigger
OFF/DO1/DO2
OFF
DI2 PRO
DI2 SP Output
Trigger
Enable DI2 SP
Output Trigger
OFF/DO1/DO2
OFF
DATE
Date
Enter the
Current Date
YY-MM-DD
/
CLK
Time
Enter the
Current Time
HH:MM:SS
/
SET ENGY
Preset Energy
Values
Preset Energy
Values
YES/NO
NO
kWh
kWh Import
Preset kWh
Import Value
0 to 99,999,999.9
0
-kWh*
kWh Export
Preset kWh
Export Value
0 to 99,999,999.9
0
kvarh
kvarh Import
Preset kvarh
Import Value
0 to 99,999,999.9
0
-kvarh*
kvarh Export
Preset kvarh
Export Value
0 to 99,999,999.9
0
kVAh
kVAh
Preset kVAh
Export Value
0 to 99,999,999.9
0
DMD SET*
Demand
Parameters
Configure
Demand
Parameters
YES/NO
NO
PERIOD
Demand
Interval
Set Demand
Interval
1, 2, 3, 5, 10, 15, 30,
60 (minutes)
15
NUM
Number of
Sliding
Windows
Set Number of
Sliding
Windows
1-15
1
EN PULSE
Energy Pulsing
Enable kWh and
kvarh Energy
Pulsing
YES/NO
NO

Table of Contents

Related product manuals