Ceiec Electric Technology
27
EN CONST
6
Pulse Constant
Pulse Constant
1k(1000)/3.2k(3200)/
5k(5000)/6.4k(6400)/
12.8k(12800)
1k
CLR ENGY
Clear Energy
Clear kWh,
kvarh and kVAh
YES/NO
NO
CLR DMD*
Clear Demand
Clear Peak
Demands
YES/NO
NO
CLR SOE
Clear SOE
Clear SOE Log
YES/NO
NO
DO CTRL
DO Control
Mode
Change DO
Control Mode
YES/NO
NO
DO1
DO1 Control
Mode
DO1 Control
Mode
NORMAL/ON/OFF
NORMAL
DO2
DO2 Control
Mode
DO2 Control
Mode
NORMAL/ON/OFF
NORMAL
CT REV
Reverse CT
Change CT
Polarity
YES/NO
NO
I1 REV
Phase A CT
Reverse Phase A
CT Polarity
YES/NO
NO
I2 REV
Phase B CT
Reverse Phase B
CT Polarity
YES/NO
NO
I3 REV
Phase C CT
Reverse Phase C
CT Polarity
YES/NO
NO
INFO
Information
(Read Only)
Check Meter
Information
YES/NO
NO
5M
Version
Firmware
Version
For example, 5M
11000 means the
meter is PMC-53M
and the firmware
version is V1.10.00.
5M means PMC-53M;
5I means PMC-53I;
5V means PMC-53V
/
PRO VER
Protocol Version
Protocol Version
e.g. 50 means V5.0
/
UPDATE
Update Date
Firmware
Update Date
e.g. 090821
/
Serial Number
Meter Serial
Number
e.g. 0811280100
/
* Available in Firmware Version V1.20.01 or later
Table 3-6 Setup Parameters
Notes:
1) The PMC-53V does not the support the DEMO Wiring Mode.
2) PT Ratio × CT Ratio × Rated Phase Voltage Input × Rated Current Input x 3 must be less than
790,000,000.