NVF5 Series User Manual Chapter 6 Parameter Function Description
Frequency highest LimitLimit max. output frequencymotor is not allowed to run over
the highest limit frequency
Frequency Lowest LimitLimit min. output frequencymotor is not allowed to run
below the lowest limit frequency
Max. Output FrequencyLimit the Max. output frequency.
Code Name Default Setting Range Description
F0.07
Max. Output
Frequency
50.00 Hz F0.08 600.00Hz -
F0.08
Maximum
Frequency
50.00 Hz F0.09 F0.07 -
F0.09
Minimum
Frequency
0.00 Hz 0.00Hz F0.08 -
6.3 Start and Stop Setting
6.3.1 Start Mode
NVF5 has three starting modes: Starting from starting frequency, first braking then
starting from starting frequency, speed tracking and restart.Set parameter F1.00 to select
NVF5 start mode.
Code Name Default Setting Range Description
F1.00
Start Mode Selection
0 0 2
0 :
Start from the
starting frequency
1 : First brake and
then start from
the starting
frequency
2 : Speed tracking
(including
direction
discrimination)
and then start
F1.01
Direct starting
frequency
0.00Hz 0.00 10.00Hz -
F1.02
Starting frequency
Holding time
0. 0s 0.0 100.0s -
F1.03
DC braking current
Before starting
0.0% 0.0 100.0%
100% Inverter
Rated Current
F1.04
DC brakin time
Before starting
0.0s 0.0 100.0s -
Starting from starting frequency
- 57 -

Table of Contents

Other manuals for CHINT NVF5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CHINT NVF5 Series and is the answer not in the manual?

CHINT NVF5 Series Specifications

General IconGeneral
BrandCHINT
ModelNVF5 Series
CategoryInverter
LanguageEnglish

Related product manuals