6
Table 1: EMC Emission
AC semiconductor motor controllers and conductors
for non-motor loads
EN 60947-4-3
Emission enclosure compliant in firing mode single
cycle and phase angle if external filter fitted
EN 60947-4-3 CISPR-11
EN 55011
Class A
Group 2
Table 2: EMC Immunity
Generic standards, immunity standard for
industrial environments
EN 60947-4-3
ESD immunity EN 61000-4-2
4 kV contact discharge
8 kV air discharge
RF interference immunity
10 V/m amplitude modulated
80 MHz-1 GHz
10 V/m amplitude modulated
1.4 GHz-2 GHz
Conducted disturbance immunity
10 V/m amplitude modulated
0.15 MHz-80 MHz
Burst immunity EN 61000-4-4
2 kV power line
2 kV I/O signal line
Surge immunity EN 61000-4-4/5
PPower line-line 1 kV (level 2)
Power line-earth 2kV (level 3)
Signal line-earth 1kV (level 2)
Magnetic fields immunity EN 61000-4-8 100 A/m (level 5)
Voltage dips, short interruptions and voltage
immunity tests
EN 61000-4-11 100%U, 70%U, 40%U,
Table 3: LVD Safety
Safety requirements for electrical equipment for
measurement, control and laboratory use
EN 61010-1
UL 508
ATTENTION
This product has been designed for class A equipment. Use of the product in domestic environments may cause
radio interference, in which case the user may be required to employ additional noise mitigation methods.
Per UL, the SCCR (Short Circuit Current Rating) is 100kA for models: C4 - XXXXX - 0 - XX Suitable for use on
a circuit capable of delivering not more than 100RMS kA symmetrical, 480VAC when protected only by listed
cartridge fuses manufactured by BUSSMAN type DFJ200 non renewable (JDDZ) 200A class J current limiting
fuses.
The CE declaration of conformity is available on request.
5. Emission, Immunity and Safety Standards