December 2016
Installation & Operation Manual
ISC-Intellitrace Supervisory Controller

Questions and Answers

  • M
    mmooreAug 4, 2025
    How to clear HIGH TEMP alarm on Chromalox Controller?
    • J
      Jasmine PerryAug 4, 2025
      The 'HIGH TEMP' alarm on the Chromalox Controller indicates that the sensed temperature is higher than the Hi Temp Setpoint. The alarm will automatically clear when the sensed temperature falls below the Hi Temp Setpoint.
  • J
    Jerry HaleAug 10, 2025
    Why does LOW TEMP alarm appear on Chromalox Controller?
    • M
      mejiajenniferAug 10, 2025
      The 'LOW TEMP' alarm on the Chromalox Controller indicates that the sensed temperature is lower than the Lo Temp Setpoint. The alarm will automatically clear when the sensed temperature rises above the Lo Temp Setpoint.
  • K
    Kathy ColeAug 17, 2025
    What to do if GFEP alarm is triggered on Chromalox Controller?
    • A
      arielstewartAug 17, 2025
      The GFEP alarm on the Chromalox Controller is triggered when the sensed GFEP current exceeds the GFEP setpoint, causing a trip. If the sensed GFEP current is less than the GFEP setpoint, the output will remain at the selected output percentage. The alarm will clear automatically when the sensed GFEP current falls below the GFEP setpoint. If the output goes to 0% (OFF) while in the alarm state, it will remain off until the alarm is reset. If the output remains at the selected output percentage, a manual reset of the GFEP Alarm may be needed. The output will go to 0% (OFF) until the alarm is reset.
  • B
    beardcharlesAug 22, 2025
    How to fix HI CURRENT (LOAD) on Chromalox Controller?
    • D
      daydianeAug 22, 2025
      The 'HI CURRENT' alarm on the Chromalox Controller indicates that the sensed load current is higher than the Hi Current Setpoint. The alarm will automatically clear when the sensed load current falls below the Hi Current Setpoint.
  • S
    Samantha ShepherdAug 28, 2025
    What to do if LO CURRENT (LOAD) shows on Chromalox Controller?
    • S
      Stephen WhiteAug 28, 2025
      The 'LO CURRENT' alarm on the Chromalox Controller means the sensed load current is lower than the Lo Current Setpoint. The alarm will automatically clear when the sensed load current rises above the Lo Current Setpoint. Note that if your output is turned OFF, GFEP and Load values will not be updated.

Summary

Important Information

License Agreement

End-User License Agreement (EULA) for the IntelliTRACE Supervisory Software Product.

Safety Precautions

Introduction to IntelliTRACE

IntelliTRACE System Features

Highlights key features of the IntelliTRACE Supervisory Control system, including communication and monitoring capabilities.

System Overview

System Topography Explained

Describes the three main components of the IntelliTRACE Supervisory system and its scalability.

System Navigation

System Tree Pane Functionality

Details the System Tree Pane for visualizing and monitoring the system network and alarm status.

Main Screen Interface

System Setup & Requirements

Panel List Overview

Describes the Panel List as a concise overview of all control systems on the IntelliTRACE network.

PC Requirements

Lists the minimum computer hardware specifications for running IntelliTRACE software.

Controller Installation Guide

Provides steps for installing the IntelliTRACE Supervisory Controller program.

System Planning Considerations

Offers advice on planning the IntelliTRACE system for circuit monitoring and management.

System Configuration

Initiate Panel Network

Steps to connect IntelliTRACE panels to the network and power them up.

Planning Your IntelliTRACE System

Guidance on organizing circuits and capturing system communication and naming details.

Configuration Tabs Overview

Introduces the Setpoints, Tuning, and I/O Mapping tabs for system configuration.

Construct Your IntelliTRACE System

Security & Password Screen

Explains how to gain access to the program using login credentials and security levels.

Adding Systems to IntelliTRACE

System Edit Requirements

Details requirements for naming systems and inputting loop counts and communication details.

Connecting Systems

Connection Status & Errors

Describes the System Connected window and Communication Error window.

Programming & Editing

Setpoints Tab Usage

Details the input cells within the Setpoints Tab for configuring loop parameters.

Setpoint Configuration Details

Setpoint Tab Input Cells

Defines the input cells for Name, Setpoint, High/Low Temp, High/Low Current, GFEP, and Output.

Parameter Value Settings

Refers to the Appendix for default, minimum, and maximum settings for parameters.

Temperature Unit Setting

Explains the selection of temperature units (Fahrenheit or Celsius) in the System Tab.

Setup Navigation Note

Provides guidance on navigating between circuit groups using loop navigation buttons.

Mass Settings Features

Apply Settings Globally

Allows applying settings from one loop to all other loops within the same panel.

Synchronize Settings Across Systems

Enables applying settings from one system (panel) to other systems on the network.

Tuning Tab for Automatic Control

Control Modes: ON;OFF, PID & Autotune

Explains ON/OFF, PID control modes, and the Autotune feature for automatic control.

Soft Start Feature

I;O Mapping Tab

Sensor Mapping

Assigns one or more sensor inputs to control one or more output circuits.

Output Mapping

Assigns one or more power outputs to control one or more output circuits.

Sensor Mapping Details

Multiple Sensor Mapping

Uses a single sensor independently or combined with others to control multiple circuits.

Combining Sensing Types

Manages multiple line and/or ambient sensing control scenarios simultaneously.

Output Mapping Details

Multiple Output Mapping

Uses a single output demand value independently or combined to control multiple circuits.

Output Power Sensing

Maps single or multiple output demand values to control circuits.

System Tab Settings

AutoCycle Feature

Explains the AutoCycle feature for intermittent loop exercise during downtime.

Current Sample Settings

System Configuration Options

Display Configuration

Reporting Configuration

Alarm Behavior Configuration

Security Configuration

System Connection Configuration

Event (Alarm) Log

Log Saving Procedure

Instructions on how to save the Event Log data to a file.

Faults and Alarms

Clearing Alarms

Explains how to clear various alarm conditions, except for Communications and Latched GFEP.

Alarm Troubleshooting

Appendix

Parameter Settings Chart

Reference chart for parameter settings, including default, minimum, and maximum values.

Wiring Considerations

Guidelines for Ethernet cable usage, maximum distance, and network connectivity.

Service Contact Information

Limited Warranty Information

Provides a link to the Chromalox limited warranty applicable to the product.

Chromalox IntelliTRACE Specifications

General IconGeneral
Control ModeON/OFF, PID
DisplayLCD
InputRTD, Thermocouple
OutputRelay, SSR
CommunicationModbus
Enclosure RatingNEMA 4X (IP66)
Communication ProtocolModbus RTU
DimensionsVaries by model
WeightVaries by model
TypeTemperature Controller
Maximum CurrentDepends on model
Temperature RangeDepends on sensor type