EN - 18
Access
level
No. Description Setting Default Display conditions
OUTPUTS (continued)
1
477 State of circuit 2 fan stage 3 If P2 = 2
1
478 State of circuit 2 fan stage 4 If P2 = 2 and P8 > 2500
1
479 State of circuit 2 fan stage 5 If P2 = 2 and P8 > 2500
1
480 State of circuit 2 fan stage 6 If P2 = 2 and P8 > 2800
1
481 State of compressor 2 winding 1
1
482 State of compressor 2 winding 2
1
485 Compressor 2 reset
1
486 Compressor 2 intake valve state
1
487 Compressor 2 exhaust valve state
1
488 Circuit 2 liquid valve state
1
489 Circuit 2 HPS valve state
1
490 State of circuit 3 fan stage 1
If P2 = 2 and P2 = 3
1
491 State of circuit 3 fan stage 2
If P2 = 2 and P2 = 3
1
492 State of circuit 3 fan stage 3
If P2 = 2 and P2 = 3
1
493 State of circuit 3 fan stage 4
If P2 = 2 and P2 = 3
1
494 State of circuit 3 fan stage 5
If P2 = 2 and P2 = 3
1
495 State of circuit 3 fan stage 6
If P2 = 2 and P2 = 3
1
496 State of compressor 3 winding 1 If P3 = 3
1
497 State of compressor 3 winding 2 If P3 = 3
1
500 Compressor 3 reset If P3 = 3
1
501 Compressor 3 intake valve state If P3 = 3
1
502 Compressor 3 exhaust valve state If P3 = 3
1
503 Circuit 3 liquid valve state If P3 = 3
1
504 Circuit 3 HPS valve state If P3 = 3
1
555 CPU version number
1
556 Console version number
*
1
557.2 ADD3 board version number If P3 = 3
1
557.3 ADD3 board version number (circuit 3) If P3 = 3
1
557.4 ADD1 board version number (circuit 3) P3 = 3
1
570 "SO" order number To be entered via a PC
1
571 MO number To be entered via a PC
1
572 Machine identification name To be entered via a PC
1
573 Machine identification number To be entered via a PC
COMMUNICATION
1
700 Communication protocol ModBus ModBus
1
701 Transmission speed Jbus: 4800 or 9600 baud (adjustable) 9600 baud
1
702 Parity Without, even or odd Without
1
703 Number of stop bits 1 or 2 1
1
704 Swapped real number format Yes or No YES
1
705 Bus Number 0 to 255 1
MASTER/SLAVE (2 MACHINES)
2
800 Master machine on loop Yes/No No If P28 = Yes
2
801 Backup machine Yes/No No
If P28 = Yes
2
802 Switch backup machine Yes/No No
If P28 = Yes
2
803 Name of backup machine Master/Slave Slave
If P28 = Yes
2
804 Loop control mode C
ASCADE or PARALLEL or PROGRESSIVE CASCADE
If P28 = Yes
2
805 Machine differential 0.5 to 5°C 1.5
If P28 = Yes
2
806 Differential between machines 1 to 10°C 4.0
If P28 = Yes
2
807 Maximum differential, additional machine 1 to 10°C 0.0 If P801 = Yes
2
808 Time delay between machines 0 to 60 min. 1
If P28 = Yes
2
809 Machine 1 'on' authorisation Yes/No Yes
If P28 = Yes
2
810 Machine 2 'on' authorisation Yes/No Yes
If P28 = Yes
2
811 Pump turned off by control
No
Yes, except for one
Yes: stop machine
No