CIAT XtraConnect 2 - HP with acoustic optimisation; HP with energy optimisation

CIAT XtraConnect 2
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN - 51
HP bar
Refrigerating circuit 2 Refrigerating circuit 1
Circuit 2 0-10V output Circuit 1 0-10V output
For speed control
2
1
3
1
4
1
2
1
3
1
4
1
HP with acoustic optimisation
P21 = 2 with acoustic optimisation
Default value of P181:
5 to 13 bar (resolution: 0.1) if P1=R134a, Default value: 8
Default value of P182: 25°C
Standard control applies to the other parameters.
1 V-frame condenser fan module per circuit = 1 stage (1 fan) with speed control + 1 single-speed stage (same as standard)
2 V-frame condenser fan modules per circuit = 1 stage (2 fans) with speed control + 2 single-speed stages (same as standard)
3 V-frame condenser fan modules per circuit = 1 stage (3 fans) with speed control + 3 single-speed stages (same as standard)
4 V-frame condenser fan modules per circuit = 1 stage (4 fans) with speed control + 3 single-speed stages (same as standard)
HP with energy optimisation
P21 = 3 With energy optimisation (available only with an electronic expansion valve)
If 4 stages: 10-25-40% and 60-75-90% for stages 2-3-4
If 3 stages: 15-30% and 70-85% for stages 2-3
If 2 stages: 20 and 80% for stage 2
The settings of parameters P181, P182, P185, P187 and P189 must be reset.
P181 = 6.8 b
P185 = 3.8 b
P182 = 30°C
In this case, parameters P181, P185, P187 and P189 can be adjusted in increments of 0.1.
Parameters P186, P188 and P190 are not necessary and therefore made inaccessible.
LX 2800 with one stage of three speed-controlled fans and three stages of three on/off fans per circuit:
1
2