89
Instruction Manual
AFQm
The points to be inspected are:
1.- Set the AFQm in STOP mode and open the main switch (OFF position).
2.- Wait 1 minute for the capacitors to discharge.
3.- Clean the ventilation grilles, removing the dust.
4.- Check the status and torque of the electrical connections, as well as the mechanical attachment to 
the wall.
5.- Reset the standard maintenance meter, to do so:
Access the main setup screen.
Figure 88: Main configuration screen.
Press the    Edit key and enter the password used to access the maintenance screen (Main-
tenance password: 8888).
The screen shown in Figure 89 will be displayed.
Figure 89: Maintenance screen.
Press the    key to reset the maintenance meter.