5.27.- TEMPERATURE ALARM
In this point the thresholds above which the temperature alarm (E10) is activated can be configured.
Note: The alarm must be enabled (“5.21.- ENABLING ALARMS”).
 
Press the   key to enter edit mode. It is identified by the   symbol and the flashing of the 
digits to be modified.
The parameters to be configured are:
  The Lo value: when the device exceeds this value for 30 minutes, alarm E09 is triggered, 
and if alarm E11 is enabled, the Computer SMART III device enters the No Connection status 
and activates alarm E11.
  The HI value: if the device exceeds this value for 30 seconds, alarm E09 is triggered, and 
if alarm E12 is enabled, the Computer SMART III device enters the Disconnection status and 
activates alarm E12.
 
If the device falls back under the Lo value during 10 minutes, it deactivates the alarms and returns 
to the normal operating status. 
In the No Connection status, the device does not connect the stages, but also does not disconnect 
them if the operation requires it.
In the Disconnection status, it disconnects all the stages and does not allow them to connect.
The   key increases the digit value.
The   key reduces the digit value.
The   key skips to the previous digit and the   key skips to the next digit.
Press   to validate the data; the   symbol disappears from the display.
Lo Value and HI Value: 
    Maximum value:  80ºC.
    Minimum value:  0ºC