5.13.- HYSTERESIS
The L (inductive) and C (capacitive) hysteresis values of the target cos φ are specified in this section. 
As long as the cos φ is within this range, the device does not connect any paths, but it can disconnect 
them.
 
The configuration of the hysteresis affects the four target cos φ specified.
Note: If the hysteresis is activated on the display screens, the symbol     flashes every 5 seconds.
Press the   key to enter edit mode. It is identified by the   symbol and the flashing of the 
digits to be modified.
The   key increases the digit value or shows the next option.
The   key reduces the digit value or shows the next option.
The   key skips to the previous digit and the   key skips to the next digit.
Press   to validate the data; the   symbol disappears from the display.
Maximum value: 0.10.
Minimum value: 0.00.
If the value entered is lower than the minimum value or higher than the maximum value, the backlight 
of the display flashes and the value entered is replaced with the minimum or maximum value, or with 
the last value validated.
Press the   key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen, “5.30.- SIMULATION 
SCREEN”.
87
Instruction Manual
Computer SMART III