Press the key to enter edit mode. It is identified by the symbol and the flashing of the
digits to be modified.
The key increases the digit value or shows the next option.
The key reduces the digit value or shows the next option.
The key skips to the previous parameter and the key skips to the next parameter.
Press to validate the data; the symbol disappears from the display.
Maximum value: 80ºC.
Minimum value: 0ºC.
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen, “5.30.- SIMULATION
SCREEN”.
5.18.- UNDERVOLTAGE TRIP
At this point we configure the voltage threshold over which the undervoltage trip function acts. This
function disables all the steps enabled in the event of any measured phase-phase voltages presenting
a value below the configured threshold. It will not enable them again until the measured phase-phase
voltages do not exceed the threshold.
91
Instruction Manual
Computer SMART III