5.4.- CONNECTION AND RECLOSING TIME
In this point the action times of the device are configured in seconds:
Ton is the minimum time between the connection and disconnection of a single stage.
TREC is the maximum time between the disconnection and connection of a single stage.
TREC must be greater than ToN; ideally, it should be 5 times greater.
Press the key to enter edit mode. It is identified by the symbol and the flashing of the
digits to be modified.
The key increases the digit value.
The key reduces the digit value.
The key skips to the previous digit and the key skips to the next digit.
Press to validate the data; the symbol disappears from the display.
Ton:
Maximum value: 999.
Minimum value: 4.
Trec:
Maximum value: 999.
Minimum value: 20.
If the value entered is lower than the minimum value or higher than the maximum value, the backlight
of the display flashes and the value entered is replaced with the minimum or maximum value, or with
the last value validated.
Press the key to access the next programming step.
If no keys are pressed for 5 minutes, the device switches to the simulation screen, 5.30.- SIMULATION
SCREEN”.
77
Instruction Manual
Computer SMART III

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Circutor Computer SMART III 6 and is the answer not in the manual?

Circutor Computer SMART III 6 Specifications

General IconGeneral
BrandCircutor
ModelComputer SMART III 6
CategoryController
LanguageEnglish

Related product manuals