Prepare Rack for Chassis Installation
Install the Cisco 8500 Switches on a standard 19 inch, Electronic Industries Alliance (EIA) rack with mounting
rails that conform to English universal hole spacing according to Section 1 of the ANSI/EIA-310-D-1992
standard.
The spacing between the posts of the rack must be (EIA-310-D-1992 19-inch rack compatible) wide enough
to accommodate the width of the chassis.
Figure 12: Rack Specification EIA (19 inches)
Table 7: Rack Specification EIA (19 inches)
Mounting Flange
Dimension (Z)
Rack Mounting Hole
Center-Center (Y)
Rack Front Opening
(X)
Rack TypePost Type
482.6mm (19”)465mm (18.312”)450.8mm (17.75”)19 inches (48.3
centimeters)
4 Post
Open Rack
version 3
Networking
(ORv3N)
Before you move the chassis or mount the chassis into the rack, we recommend that you do the following:
Procedure
Step 1 Place the rack at the location where you plan to install the chassis.
Step 2 (Optional) Secure the rack to the floor.
To bolt the rack to the floor, a floor bolt kit (also called an anchor embedment kit) is required. For information
on bolting the rack to the floor, consult a company that specializes in floor mounting kits (such as Hilti; see
Hilti.com for details). Make sure that floor mounting bolts are accessible, especially if annual retorquing of
bolts is required.
Note
Hardware Installation Guide for Cisco 8500 Switches
20
Prepare for Installation
Prepare Rack for Chassis Installation