CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Tranquility
®
Water-to-Water (TMW) Series
Rev.: 04/15/16
16
ClimateMaster Water-Source Heat Pumps
Electrical - Line Voltage
TMW Electrical Data
ELECTRICAL - LOW VOLTAGE
Thermostat Connections - The aquastat/thermostat
should be wired directly to the CXM/DXM board #1.
Note: The TMW second stage is wired directly to the
CXM #2.
Low Water Temperature Cutout - LT1 - The CXM/
DXM control allows the eld selection of source uid
low temperature cutout points. The factory setting of
LT1 is set for water (35°F [1.7°C]). In cold temperature
applications jumper JW3 (LT1- antifreeze 15°F [-9.4°C])
should be clipped as shown in Figure 4 to change the
setting to 10°F [-12.2°C], a more suitable temperature
when using antifreezes. Never clip JW3 prior to antifreeze
being added to the loop.
LT1
LT2
Figure 4: Changing LT1-Low Water Temperature
Cutout Setpoint
CXM PCB
JW3-LT1 jumper
should be clipped
when antifreeze is
used.
Model
Voltage
Code
Voltage
Voltage Min/
Max
Compressor
Total Unit
FLA
Min Circuit
Amps
Max
Fuse/
HACR
Qty RLA LRA
TMW036
G 208-230/60/1 187/254 1 16.7 79 16.7 20.8 35
E 265/60/1 239/292 1 13.5 72 13.5 16.8 30
H 208-230/60/3 187/254 1 10.4 73 10.4 13.1 20
F 460/60/3 414/506 1 5.8 38 5.8 7.2 15
N 575/60/3 518/633 1 3.8 36.5 3.8 4.7 15
V 220-240/50/1 198/264 1 13.5 67 13.5 16.9 30
U 380-420/50/3 342/462 1 5.4 38 5.4 6.8 15
TMW060 B
G 208-230/60/1 187/254 1 26.3 134 26.3 32.9 50
H 208-230/60/3 187/254 1 15.6 110 15.6 19.5 35
F 460/60/3 414/506 1 7.8 52 7.8 9.8 15
N 575/60/3 518/633 1 5.8 38.9 5.8 7.3 15
U 380-420/50/3 342/462 1 7.8 51.5 7.8 9.8 15
TMW120 B
G 208-230/60/1 187/254 2 26.3 134 52.6 59.2 80
H 208-230/60/3 187/254 2 15.6 110 31.2 35.1 50
F 460/60/3 414/506 2 7.8 52 15.6 17.6 25
N 575/60/3 518/633 2 5.8 38.9 11.6 13.1 15
U 380-420/50/3 342/462 2 7.8 51.5 15.6 17.6 25
TMW170
H 208-230/60/3 187/254 1 53.6 245 53.6 67.0 110
F 460/60/3 414/506 1 20.7 125 20.7 25.9 45
N 575/60/3 518/633 1 16.4 100 16.4 20.5 35
U 380-420/50/3 342/462 1 20.7 118 20.7 25.9 45
TMW340
H 208-230/60/3 187/254 2 53.6 245 107.2 120.6 150
F 460/60/3 414/506 2 20.7 125 41.4 46.6 60
N 575/60/3 518/633 2 16.4 100 32.8 36.9 50
U 380-420/50/3 342/462 2 20.7 118 41.4 46.6 60