34
Data Register Locations at CODEL Tunnel Tech 700 Series AQM for Interrogation using Standard
MODBUS
Register Format
Customer Specific Details
Location
Details
Data
Units
Typical Range
Value
0070
NOppm
XXXX
1ppm
0-30ppm
XXXX
0071
COppm
XXXX
1ppm
0-300ppm
XXXX
0072
Opacity
XXXX
0.01%
0-100%
XXXX
0073
MOR
XXXX
1m
0-9999m
XXXX
0074
Visibility dimming coefficient
XXXX
0.0001m-1
0-0.015m-1
XXXX
0075
Visibility transmissivity
XXXX
0.01%
0-100.00%
XXXX
0076
CO/NO detector validation
XXXX
Logic
0000=valid, det. error if >0000
XXXX
0077
Visibility detector validation/Cal in progress
XXXX
Logic
0000=valid, 01XX det. er, XX01 Cal
XXXX
0078
CO detector validation/Cal in progress
XXXX
Logic
0000=valid, 01XX det. er, XX01 Cal
XXXX
0079
Not used
XXXX
-
-
XXXX
007A
Not used
XXXX
-
-
XXXX
007B
Not used
XXXX
-
-
XXXX
007C
Not used
XXXX
-
-
XXXX
007D
Not used
XXXX
-
-
XXXX
007E
Head identifier
XX01
Integer
Constant
XX01

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CODEL Tunnel Tech 700 Series and is the answer not in the manual?

CODEL Tunnel Tech 700 Series Specifications

General IconGeneral
BrandCODEL
ModelTunnel Tech 700 Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals