InteliATS
NT
STD, SW version 2.0, ©ComAp – June 2010 40
IA-NT- STD-2.0-Reference Guide.pdf
Engine start evaluation diagram:
MinStabTime [s]
Minimum time interval between defined generator voltage is reached to GCB is cl
If BI: GenReadyToLoad is not configured, timer is not used.
Step: 1s
: 1 – 300 s
osed.
Stop Time
troller how long should it wait for the
ToLoad signal is deactivated or
he stop time expires the Trp Stop
i controller sends Stop command to
(S
Step: 1s
Range: – 3601 sec Value 360 n he controller doesn’t care for the engine is
stopped (Trp Stop Fail is never announced).
GenStart Logic [CLOSE-ON/CLOSE-OFF]
The set point influences the behavior of the output Gen Start/Stop.
CLOSE-ON: Gen-set should start when the output Gen Start/Stop is closed.
CLOSE-OFF: Gen-set should start when the output Gen Start/Stop is opened.
Range
[s]
Period given by the value of the Stop Time setpoint tells the con
engine to change to to te (stop state means GenReady the s p sta
r vgenerato oltages disappeared). If the engine is still running after t
Fail alarm s announced. Stop Fail starts counting always when the
the engine tart/Stop output is deactivated).
0 1 mea s t