STD, SW version 2.0, ©ComAp – June 2010 39
IA-NT- STD-2.0-Reference Guide.pdf
s Setpoint
Password
EnterPassword
Password is a four-digit number. Password enables change of relevant protected setpoints.
key to enter the password. Use ↑ or ↓ keys to set and ENTER
NOTE:
There is only 1 level of a password.
ChangePassword
Use ↑ or ↓ keys to set and ENTER key to change the password.
NOTE:
At first the password has to be entered before the new password can be changed.
Basic Settings
ControllerN ma e
NT
User de d namefine , used for Inteli identification at remote phone or mobile connection.
llerN 14 characters long and have to be entered using LiteEdit software.
eq [Hz]
: 65 Hz
e [s]
ut prior to the engine start.
zero t to leave the output Prestart/Pretzransfer open.
:
MaxStartDel [s]
This timeout starts after closing binary output GEN START/STOP. When generator does not reach
defined limits Basic Settings: Nominal Freq) within MaxStartDel, Trp Start Fail alarm occurs and the
gen-set will shut down. See the table below for a description of the engine start evaluation.
If MaxStartDel is longer then 600 s it means there is NO TIMEOUT.
Step: 1s
Range: 0 – 600 s, 601 s = NO TIMEOUT
Contro ame is max
Nominal Fr
Nominal generator frequency (usually 50 or 60 Hz )
1Hz Step:
Range 45 –
Prestart Tim
Tim inge of clos of the Prestart and/or Pretransfer outp
Set to if you wan
Step: 1s
Range: 0 – 600 s
Cooling Time [s]
e stop. Runtime of the unloaded gen-set to cool the engine befor
1s Step:
Range 0 – 3600 s