STD, SW version 2.0, ©ComAp – June 2010 41
IA-NT- STD-2.0-Reference Guide.pdf
[V]
th
setpoint expires, the engine is started and is running as long as
setpoint. Test Period starts counting always when the engine is stopped.
da s
[min]
when engine is running after expiring the Test Period setpoint.
Batt Undervolt
Warning reshold for low battery voltage.
Step: 0,1 V
Range: 8V – 40 (Battery >Volts)
Test Period [d]
After the given value of Test Period
the value of Test Duration
Range: 0 – 240 y
^ Available only in AMF8, 9.
Test Duration
Time interval,
Range: 0 – 240 minutes
^ Available only in AMF8, 9.
NOTE:
This function does not work till both setpoints (Test Period and Test Duration) are set to non-zero
values.
AMF Settings
EmergStart Del [s]
the gen-set
s
Transfer Del [s]
Delay after GCB opening to MCB closing during the return procedure.
Delay after MCB opening to GCB closing if the setpoint MCB Opens On set to GENRUN
Step: 0.1s
Range: 0 – 600.0 s
The time charts bellow show recommended setting of AMF Settings: Transfer Del setpoint.
Delay after the mains failure to the start of
Step: 1s
Range: 0 – 6000
MainsReturnDel [s]
Delay after the mains return to the GCB opening.
Step: 1s
Range: 1 – 3600 s