EasyManuals Logo

ComAp InteliATS NT STD User Manual

ComAp InteliATS NT STD
58 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background image
InteliATS
NT
STD, SW version 2.0, ©ComAp – June 2010 41
IA-NT- STD-2.0-Reference Guide.pdf
[V]
th
setpoint expires, the engine is started and is running as long as
setpoint. Test Period starts counting always when the engine is stopped.
da s
[min]
when engine is running after expiring the Test Period setpoint.
Batt Undervolt
Warning reshold for low battery voltage.
Step: 0,1 V
Range: 8V – 40 (Battery >Volts)
Test Period [d]
After the given value of Test Period
the value of Test Duration
Range: 0 – 240 y
^ Available only in AMF8, 9.
Test Duration
Time interval,
Range: 0 – 240 minutes
^ Available only in AMF8, 9.
NOTE:
This function does not work till both setpoints (Test Period and Test Duration) are set to non-zero
values.
AMF Settings
EmergStart Del [s]
the gen-set
s
Transfer Del [s]
Delay after GCB opening to MCB closing during the return procedure.
Delay after MCB opening to GCB closing if the setpoint MCB Opens On set to GENRUN
Step: 0.1s
Range: 0 – 600.0 s
The time charts bellow show recommended setting of AMF Settings: Transfer Del setpoint.
Delay after the mains failure to the start of
Step: 1s
Range: 0 – 6000
MainsReturnDel [s]
Delay after the mains return to the GCB opening.
Step: 1s
Range: 1 – 3600 s

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliATS NT STD and is the answer not in the manual?

ComAp InteliATS NT STD Specifications

General IconGeneral
BrandComAp
ModelInteliATS NT STD
CategoryController
LanguageEnglish

Related product manuals