Up to 10 meters: r local
the three wires
communication:
L-NT/ID-Lite connector (D-SUB9 fem IL-NT-RD connector (D-SUB9 female)
Recommended to use standard Null-modem cable fo
connection between controller and remote display, although
(TxD, RxD, GND) RS 232 connection is enough for direct
IA-NT/I ale)
RxD 2 3 TxD
TxD 3 2 RxD
GND 5 5 GND
Remote RS485 and/or direct RS232 connection
HW module: IL-NT-RS232-485
Up to 1000 meters (only with RS485):
Case 1) RS232 / Master controller settings:
ControllerAddr = 1..32
ECT
COM2 Mode = DIRECT
Case 3) S232 + RS485 / Master controller settings:
ControllerAddr = 1..32
COM1 Mode = DIRECT
COM2 Mode = DIRECT
It is possible to make a RS232 direct connection with IL-NT-RS232 module on one side and IL-NT-
RS232-485 module on the other side.
COM1 Mode = DIR
Case 2) RS485 / Master controller settings:
ControllerAddr = 1..32
R