InteliLite Global Guide
140
Reading binary inputs as coil status.
Table: Binaries
Allowed MODBUS functions: 01, 02
Addresses
Modbus Addr.
Prot. Addr.
Source
= Value
= State
C.O.#
State #
Name of Value
Name of State
Bit #
Bit Name
Activated by protection(s):
Group
00000 Value 8235 Binary Inputs 1 GCB Feedback Controller I/O
00001 Value 8235 Binary Inputs 2 MCB Feedback Controller I/O
00002 Value 8235 Binary Inputs 3 Emergency Stop Controller I/O
We will read state of MCB Feedback binary input.
Request: (Numbers in Hex)
01 01 00 01 00 01 AC 0A
Controller address Modbus function
Register address
0001
hex
= 0001
dec
Number of registers CRC
Response: (Numbers in Hex)
01 01 01 01 90 48
Controller address Modbus function
Length of data
01
hex
= 1 byte read
Data
01
hex
= active
CRC
The readed data is 01, it means this binary input is active.
Note: You can use modbus function 2 insted of 1, rest of data remains same (CRC differs).

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals