InteliLite Global Guide
133
SNMP notifications
Except the request-response communication model, in which the communication is controlled by the Manager,
there are also messages that the Agent sends without any requests. These messages are called „Notifications“
and inform the Manager about significant events occurred in the Agent.
The controller can send notifications to two different SNMP Managers (two different IP addresses). The
addresses are to be adjusted in the CM-Ethernet setpoint group by the setpoints SNMP Traps IP Address 1 (page
336) and SNMP Traps IP Address 2 (page 336). If the Manager address is not adjusted the particular notification
channel is off. The controller will send the notifications in format adjusted by the setpoint SNMP Trap Format.
Each notification (kind of event) is identified by an unique identifier (Trap ID in SNMPv1 or Notification OID
in SNMPv2). This unique identifier gives the specific meaning to the notification message, e.g. Protection 1.
level - Fuel Level - alarm activated.
All possible notifications and their identifiers are listed in the MIB table.
The notification message also contains controller name, serial number and textual description of the event.
6.2.2 MODBUS-RTU, MODBUS/TCP
MODBUS protocol is used for integration of the controller into a building management system
or for remote monitoring via 3rd party monitoring tools.
MODBUS-RTU can be used on serial interfaces (CM-RS232-485 module is required). The MODBUS-RTU
server must be activated by switching the setpoint COM1 Mode (page 300) or COM2 Mode (page 301) into
the Modbus position. The serial speed for MODBUS-RTU communication is to be adjusted by the setpoint
COM1 MODBUS Communication Speed (page 301) or COM2 MODBUS Communication Speed (page 302).
MODBUS/TCP can be used on the ethernet interface (CM-Ethernet module is required). Up to 2 clients can
be connected simultaneously. The MODBUS/TCP server must be activated by the setpoint MODBUS Server
(page 335).
MODBUS, MODBUS/TCP protocol can be used simultaneously with Web connection and direct
ethernet/AirGate connection.
The MODBUS, MODBUS/TCP protocol is enabled alternatively with the SNMP protocol, so both protocols can
not be active simultaneously.
Addres space
The object address space is separated into several areas as described in the table below. The actual mapping of
specific controller data objects to specific MODBUS addresses, which depends on configuration, can be
exported into a text file from the appropriate controller archive using LiteEdit2015. There are several special
registers with fixed meaning (reserved registers) which are listed in a separate table in this chapter.
MODBUS
address
Meaning Access
MODICON object
type
MODBUS function
0000 .. 0999 Binary objects Read only Discrete Inputs
Read: 01, 02
1000 .. 2999 Values Read only
Input Registers
Read: 03, 04

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals