301
Setpoint group CM-RS232-485 Related FW 1.2.1
Range [units] 9600 / 19200 / 38400 / 57600 / 115200 [bps]
Default value 9600 bps Alternative config NO
Step [-]
Comm object 24477 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint COM1 Mode (page
300)
Description
If the MODBUS mode is selected on COM1 channel, the MODBUS communication speed can be adjusted
here.
COM1 MODBUS Communication Speed
6 List of setpoints (page 150)
Setpoint group CM-RS232-485 Related FW 1.2.1
Range [units] Direct / MODBUS [-]
Default value Direct Alternative config NO
Step [-]
Comm object 24451 Related applications AMF, MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
Communication protocol switch for the COM2 channel.
Direct LiteEdit2015 communication protocol via serial cable.
MODBUS MODBUS protocol.
COM2 Mode
6 back to List of setpoints
Setpoint group CM-RS232-485 Related FW 1.2.1
Range [units] 9600 / 19200 / 38400 / 57600 / 115200[bps]
Default value 57600 bps Alternative config NO
Step [-]
Comm object 24340 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Only if relevant module is installed + conditioned by the setpoint COM2 Mode (page
301)
Description
If the direct mode is selected on COM2 channel, the direct communication speed of controller part of line can
be adjusted here. Speed of second part of line has to be adjusted to the same value.
COM2 Communication Speed
6 List of setpoints (page 150)