InteliLite Global Guide
288
Setpoint group Plug-In Modules Related FW 1.2.1
Range [units] ENABLED / DISABLED [-]
Default value ENABLED Alternative config NO
Step [-]
Comm object 24279 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint enable or disable module in slot B.
Slot B
6 back to List of setpoints
Group: Sensors Spec
Subgroup: Analog Input 1
Setpoint group Sensors Spec Related FW 1.2.1
Range [units] the range is defined by analog sensor curve
Default value
0 (number of decimal is
given by sensor curve)
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 8431 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Calibrating constant to adjust the measured value of controller analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Note: Unit is adjusted via LiteEdit2015 in configuration of analog input 1.
Analog Input 1 Calibration
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals