InteliLite Global Guide
569
Alarm Type Warning
Alarmlist message Wrn Fuel Level
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the fuel level is lower than the level set in Fuel Level Wrn
(page 183) setpoint.
Wrn Fuel Level
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Fuel Thief
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm occurs when the fuel level value measured at relevant AI (Fuel Level)
drops faster than is the limit adjusted by setpoint Maximal Fuel Drop (page 185).
Wrn Fuel Thief
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn + Name of analog input 1
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that value the general analog protection is out of warning
protection limit.
Wrn AIN Prot
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn + Name of binary input
Alarm evaluated All the time
Related applications AMF, MRS
Description
Binary input also can be adjusted like alarm. In this case message in alarmlist
contains prefix - Wrn and binary input name. This alarm occurs, when appropriate
binary input is active.
Wrn BIN Protection 1..48
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator L1 > Voltage
Alarm evaluated Generator excited only
Wrn Generator L1 > Voltage