InteliPro, SW version 1.0, ©ComAp – May 2011 
InteliPro Reference Guide 
4-11
ROCOF Prot 
Separate output for ROCOF protection. 
DOC Prot 
Separate output for directional overcurrent protection. 
P Prot 
Separate output for mains reverse power protection. 
I> Prot 
Separate output for overcurrent (ANSI 50 and 51) protection. 
NVD Prot 
Separate output for neutral voltage displacement protection. 
!NVD Prot 
Separate output for inverted signal of Neutral Voltage Displacement protection. 
EFC Prot 
Separate output for earth fault current (ANSI 50N and 51N) protection. 
IGS Prot 
Separate output for ground surge current (ANSI 50GS and 51GS) protection. 
I Unb Prot 
Separate output for current unbalance protection. 
DC Healthy 
The output is closed all the time when auxiliary voltage is within the limits (Aux protect: Aux >V 
and Aux protect: Aux <V). The output opens when Aux voltage is failed or out of setpoint limits. 
Watchdog 
The output is closed all the time of controller’s operation. When the watchdog event occurs the output. 
The alarm message “Wrn Watchdog” is displayed and the output Watchdog stays opened after the 
controller’s restart due to watchdog reset of the controller until the Fault Reset 
 button is pushed. 
MaxParTime 
Separate output of the short term parallel protection closes after the timer MaxParallTime has elapsed 
and both CB1 Feedback and CB2 Feedback remain closed. 
!MaxParTime 
Separate output for inverted signal of short term parallel protection. 
U Sig 
Signalling output of "out of limit" voltage according to the setting in V<> group. 
Activates immediately in the moment of fault conditions (does not wait until delay times out). 
Deactivates in the moment when the measured values are back in limits. Fault reset has no effect on 
this output. 
f Sig 
Signalling output of "out of limit" frequency according to the setting in f<> group.