4-35
Technical data
Power supply
Power supply range 8-36VDC
Power supply drop-out
immunity
50ms (from min. 10V)
Power consumption cca 200mA/8V; 50mA/36V
Peak power consumption
(LT)
cca 0,56A/8V; 1,8A/36V
Backup battery type CR 1225
Estimated backup battery
lifetime
10 years
Operating conditions
Operating temperature -20... 70°C
Operating temperature (LT
version)
-40... 70°C
Operating humidity 95% non-condensing (IEC/EN 60068-2-30)
Protection degree (front
panel)
IP65
Vibration 5-25Hz, +/- 1.6mm; 25-100Hz, a = 4g
Shocks a
max
200m/s
2
Storage temperature -30... 80°C
Intended use according to
UL 508 standard
InteliPro is intended for use with switchgear and
associated equipment as per the category for Protective relays –
NRGU
Physical dimensions
Dimensions 185x125x60mm (WxHxD)
Weight
Mounting cutout size 175x115mm (WxH)
Standard conformity
Electromagnetic
compatibility
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4
Low voltage directive EN 61010-1:95 +A1:97
Binary inputs
Number of binary inputs 9
Galvanic insulation Not insulated
Common pole Positive, V
s
= 8-36VDC
Closed contact voltage <2V
Open contact voltage 4V - V
s