InteliPro Reference Guide 
4-34
Date/Time 
TimeStamp Per  [ min ] 
Time interval for history record. Time base is based on number of minutes since midnight. History 
records are only made in parallel, if CB1 Feedback and CB2 Feedback are configured and closed, 
activation delay elapsed and if there is at least one unblocked protection. If CB1 Feedback and CB2 
Feedback are not configured, history records are made in case that there is at least one unblocked 
protection. 
Step: 1 min 
Range:  0 - 240 min 
0 = OFF, TimeStamp event is disabled 
Default setting: 30 min 
#SummerTimeMod [DISABLED / WINTER / SUMMER, WINTER-S, 
SUMMER-S]  
DISABLED:  Automatic switching between summer and wintertime is disabled. 
WINTER (SUMMER):  Automatic switching between summer and wintertime is enabled and it is 
set to winter (summer) season. 
WINTER-S (SUMMER-S):  Modification for southern hemisphere. 
Default setting: DISABLED 
Note:
 
In case of interconnection of InteliPro with other ComAp units on the CAN2 bus, the setpoint is 
automatically synchronized within the interconnected group. 
#Time [HHMMSS] 
Real time clock adjustment. 
Note:
 
In case of interconnection of InteliPro with other ComAp units on the CAN2 bus, the setpoint is 
automatically synchronized within the interconnected group. 
#Date  [DDMMYY] 
Actual date adjustment 
Note:
 
In case of interconnection of InteliPro with other ComAp units on the CAN2 bus, the setpoint is 
automatically synchronized within the interconnected group. 
Sensors Spec 
AI1Calibration, AI2Calibration, AI3Calibration, IOM AI1 Calibr, IOM AI2 
Calibr, IOM AI3 Calibr, IOM AI4 Calibr 
The value for calibration of the appropriate analog input of the unit or extension module IG-IOM or 
IGS-PTM. This value is added to the output of analog input curve.