InteliPro, SW version 1.0, ©ComAp – May 2011 
InteliPro Reference Guide 
4-36
Input resistance  4,2 kOhm 
Binary outputs 
Number of binary outputs  8 
Galvanic insulation  Not insulated 
Type  Transistor, switching to negative supply terminal 
Operating voltage  8-36VDC 
Switching current  500mA (suppresion diodes required for inductive loads) 
Analog inputs 
Number of analog inputs  3 
Galvanic insulation  Not insulated 
Electrical range  0-2500ohm 
Resolution 10bits, 4digits 
Supported sensor types 
Predefined: VDO 10Bar, VDO Temperature, VDO Fuel level 
User defined: 10 points non-linear sensors can be defined by the 
user  
Precision  1% from the range 
Mains measurements 
Measurement inputs  3ph mains voltage, 3ph mains current, NVD voltage, Sync Check 
Measurement type  True RMS 
Voltage range  480V Ph-Ph (277V Ph-N) 
Max. measured voltage  340V Ph-N 
Voltage accuracy  1% from the range 
Current range  5A 
Max. measured current  9A 
Max. allowed current  12A continous, 50A/1s 
Current accuracy  2% from the range 
CT input burden  <0.5VA 
Frequency range  30-70Hz, measured from L3 
Frequency accuracy  0.05Hz 
Remote communication interface 
RS232  Optional using the plug-in module IL-NT-RS232, D-SUB9M socket 
RS485 
Optional using the plug-in module IL-NT-RS232-485, plug-in 
terminal block 
Baud rate  Depending on selected mode (up to 57600 bps) 
USB  Optional using the plug-in module IL-NT-S-USB 
Ethernet  Optional using the plug-in module IB-Lite 
Extesion modules interface 
Type CAN bus 
Galvanic insulation  Insulated, 500V