InteliPro, SW version 1.0, ©ComAp – May 2011
InteliPro Reference Guide
4-26
IMinDiffEval [ % ]
Minimum limit of measured current in % of nominal current, that the current unballance is enabled
from. The value is evaluated as an average value of all phase currents.
Step: 1 %
Range: 0 - 100 % of NominMainsCurr
Default setting: 50 %
I Unb Del [ s ]
Delay of current unbalance protection.
Step: 0,1 s
Range: 0.0 - 600 s
Default setting: 5,0 s
I Unb Block BI [ Block 1 / Block 2 / Block 1+2 / None ]
Selection of blocking binary input for current unballance protection.
Default setting: None
I> V Trp BO [ Trp 1 / Trp 2 / Trp 1+2 / None ]
Selection of trip binary output for current unballance protection.
Default setting: None
DOC
NominGenCurr [ A ]
Nominal current of the generator(s) connected to the mains feeder, protected by the InteliPro unit.
Serves for directional overcurrent protection evaluation.
Step: 1 A
Range: 1 - 32000 A
Default setting: 288 A
DOC> [ % ]
Threshold for directional overcurrent evaluation as the % level of NominGenCurr.
Step: 1 %
Range: 0 - 150 %
0 = OFF, the directional overcurrent protection is disabled
Default setting: 50 %
DOC> Del [ s ]
Delay for directional overcurrent.
Step: 0,1 s
Range: 0,0 - 30 s
Default setting: 5,0 s
DOC Test [ DISABLED / ENABLED ]
Enables/disables the testing mode of directional overcurrent protection. When ENABLED, the output
DOC TEST shows the sensing of the protection regardless of other protection enabling/disabling
conditions. Activating DOC test does blocks the regular function of the ANSI 67 directional
overcurrent protection stage!
DISABLED: protection test disabled
ENABLED: protection test enabled Enabling the DOC test does blocks the regular function of the
ANSI 67 directional overcurrent protection stage!
Default setting: DISABLED