6. USAGE IN EXPLOSION DANGEROUS AREAS
The ST450EC is explosion proof certified according to:
II 2G Ex d IIC T6 Gb
II 2D Ex tb IIIC T85°C Db
Ex d IIC T6 Gb
Ex tb IIIC T85°C Db
Certificate number KIWA 16ATEX0008 X, IECEx KIWA 16.0003X. The method of usage as
mentioned in the certificate is binding.
Modifications made to the device as well as the use of other, non-original, components are not
permitted.
Repairs or part replacements should only be carried out in a non-explosive atmospheres and
should only be performed by a Consilium trained and authorised service technician.
The ST450EC gas detector should be connected to the gas detection control system according
to the wiring diagram as given in chapter 2 - INSTALLATION. The earth connection, as
mentioned in the wiring diagram, should be a clean earth connection.
For more information about flameproof joints, please contact Consilium.
The Consilium splashguard accessory may store an ignition capable level of electrostatic
charge in an IIC and a IIIC environment. The type labels on the enclosures may store an ignition
capable level of electrostatic charge in an IIIC environment. Therefore the user/installer must
implement precautions to prevent the build-up of electrostatic charge, i.e. locate the
equipment where a charge-generating mechanism (such as wind-blown) is unlikely to be
present and clean with a damp cloth (not with a dry cloth)
7. LIABILITY IN CASE OF DAMAGES
During use and maintenance of the ST450EC one must follow this guide and maintain as
instructed.
The instrument should only be used in applications as described in this manual. In case of
repairs, only original Consilium parts should be used.
Consilium, nor Buveco, is not liable for any damages caused through usage of the ST450EC,
when the system is used in other applications or in another ways then those described in the
manual.
The same will apply for maintenance and repairs which are not carried out by the Consilium
service department or by a Consilium authorised service centre. Likewise, Consilium, nor it
subsidiary Buveco, will assume no liability for any caused damages and the warranty will be
voided in these cases.