9. PARTS AND ACCESSORIES
The following optional parts and accessories are available for the Consilium ST650EX / ST650-
CO
2
/ ST350EX sensing heads:
ST650EX:
Spare gas sensor Part no. Range Description
BUSENS D, type 3 1212200 0-100 %LEL CH
4
* Gas sensor for standard applications
BUSENS, type HT Remote 9220032 0-100 %LEL CH
4
*
High temperature, applications up to
120°C ambient temperature
BUSENS D, type 25 1212203 0-100 %LEL
Gas sensor for combustible vapours
containing halogens
BUSENS D, type 41 1212204
0-100 %LEL Gasoline
0-100 %LEL Kerosene
0-10 %LEL NH
3
Kerosene and Gasoline applications,
range 0-100 %LEL
Ammonia applications, range 0-10 %LEL
BUSENS D, type 6 (TCD) 1212205 0-100 Vol.% CH
4
*
Thermal Conductivity sensor,
measurements up to 0-100 Vol.% CH
4
BUSENS D, type IRs CH
4
1219622 0-100 %LEL CH
4
Infrared sensor (NDIR), Methane
BUSENS D, type IRs C
3
H
8
1219623 0-100 %LEL C
3
H
8
* Infrared sensor (NDIR), Propane
* Standard range / target gas, sensor suitable for different target gasses (depending on calibration).
A gas detector provided with a catalytic bead sensor is also not suitable in areas
where silicon compounds, organometallic compounds, organic phosphate esters,
halogen-containing hydrocarbons and sulphur compounds are present. These
environmental factors may significantly reduce the life of the sensor.
ST650-CO
2
:
Spare gas sensor Part no. Range Description
BUSENS D, type IRs CO
2
1219620
0-1 Vol. % CO
2
0-5 Vol. % CO
2
0-10 Vol. % CO
2
0-100 Vol. % CO
2
Infrared sensor (NDIR), Carbon dioxide
ST350EX:
Spare gas sensor Part no. Range Description
BUSENS D, type SCV 1212587
Calibration
dependent
Standard applications, (Aromatic)
Hydrocarbons, ppm level
BUSENS D, type SCF 1212582
Calibration
dependent
Freon applications, detection of synthetic
refrigerants
BUSENS D, type IRs
See datasheet
Calibration
dependent
Infrared sensor (NDIR), for Toxic gasses

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Consilium ST650EX and is the answer not in the manual?

Consilium ST650EX Specifications

General IconGeneral
BrandConsilium
ModelST650EX
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals