14
DC-ITD-PS7MAN01.A www.dodtec.com
JAN 2019 815-788-5200
PS-7 Manual
Chapter 6 Installation and Wiring
Warning
The Gas Detector is not explosion-proof. It must be installed in a safe location.
When detecting highly adsorbent gases remove the internal filter and install proper
end of line filter (see page 8)
The sample distance on the PS-7 is 50 feet for non-absorbent gases and 30 feet for
absorbent gases. FEP TEFLON tubing must be used with absorbent gases.
Caution
The Gas Detector should be installed in a location free from shock and vibration, and
away from sources of high frequencies or magnetism.
Do not use the gas collector hood when detecting gas concentrations in narrow spaces
such as ducts.
Do not install the Gas Detector in locations where the temperature may exceed 40°C or
dew condensation or sudden temperature fluctuations may occur.
The Gas Detector is not drip-proof.
The pressure difference between the gas inlet/exhaust ports and the ambient
atmosphere must be within 1 kPa. The pressure difference between the inlet port and
exhaust port must be such that the inlet port is a negative pressure of 1 kPa or less.
Install the Gas Detector vertically. (Inlet port and exhaust port must be in downward
direction.)
Locate the detector tip (the tip of the gas sampling pipe) to be appropriate for the
specific gravity of the gas to be detected. It must also be placed in a location where the
target gases are likely to accumulate.
Type of gas
Installation height
Heavier than air
Not more than 30 cm above floor level
Equivalent to air
75 to 150 cm above floor level
Lighter than air
Near the ceiling